The Dataprobe iBoot EXP is an expansion module that adds an extra outlet to the Dataprobe iBoot G2+ or iBoot G2S. Up to an additional two iBoot EXP units can be controlled by the iBoot G2+ or G2S.

Dataprobe iBoot EXP Expansion Module

Expansion outlets for Dataprobe iBoot G2+ & iBoot G2S

The Dataprobe iBoot EXP is a remote controlled power on / off expansion switch that is controlled by Dataprobe’s iBoot G2+ or iBoot G2S web power switches. iBoot EXP is compatible with worldwide power from 105-240VAC. It can switch up to 12Amps at 120VAC and 10Amps at 220VAC. Two iBoot EXP units can be connected and independently controlled by the iBoot G2+ or iBoot G2S

Features & Benefits

Features & Benefits

  • Accees via simple web browser operation.
  • External I/O featuring: Two Inputs, Two Outputs, Screw Terminal Connections: V+ (Power In), I (Controlled Input), G (Ground) & O (Feedback Output)
  • LED Indicators: Green indicating iBoot-EXP is connected and Red that shows power outlet is on
  • UL Listed for Safety with full UL FCC / RoHS / WEEE compliance
  • AutoPing from the iBoot G2+/ iBoot G2S detects network or equipment outage and takes immediate action to restore your network or device
  • Real-time scheduling to have a fresh reboot each morning or minimise power waste at night.
  • 110/220 VAC Operation
  • Auto ranging power input. Deploy iBoot EXP anywhere in the world. iBoot EXP uses IEC320 Connectors and includes line and extension cords for North America.
  • 12 AMP Switching suitable for most Servers, Routers, Kiosks, etc. (10 Amps at 220 VAC)

Specifications

Specifications

  • Physical: H x W x D: 2.0” x 3.2” x 4.2” (60mm x 82mm x107mm)
  • Operating Temperature: 0 to 50 °C
  • Power: 105 – 240 VAC Auto Ranging
  • Power Switching: 12 Amps at 105-125 VAC | 10 Amps at 210-240 VAC Includes cables for North America (NEMA 5-15)
  • Power Connectors:
    • Power Inlet: IEC 320 C13 Plug | Linecord for North America Included: 16AWGX3C.
    • Power Out: IEC 320C14 Receptable | Extension Cord for North America Included: 16AWGX3C
  • LED Indicators: Green = OK (Power Control Available) | Red = PWR (Output Power)
  • Reliability: MTBF 540,000 Hours | Operating Cycles 10,000,000 Mechanical. 100,000 Maximum Load
  • Security: Dual Password Protected, User and Admin (Provided by iBoot-G2+/ iBoot G2S)